SUNTEC A-7000B model contains a unique and hydraulic safety cut-on/off, driven by a motor speed dependent device, and a high single pipe lift capacity. (Except A-77xx models). This unit is supplied for 1-pipe operation, without by-pass plug installed. Please verify before installation.
Compatibility :
As the motor starts, the fuel from the gearset flowing through the cone valve creates a pressure drop across the diaphragm valve. When the pressure difference is sufficient to overcome the spring force, the diaphragm valve closes and the pressure is built up causing the piston to open and the fuel flow through the nozzle port.
The piston spring is adjusted such that a given nozzle pressure can be maintained while any resulting excess fuel is dumped.
Cut-off speed is factory set so that the cone valve gives the necessary pressure drop to open the diaphragm valve. This in turn reduces the piston chamber pressure and the piston shuts off the nozzle.
One pipe installation :
The by-pass plug must not be installed. The excess fuel is returned back to the inlet.
Two pipe installation :
The steel plug of the return port must be removed and the by-pass plug must be inserted in the return port allowing excess fuel is bypassed back to the tank. The return plug must not be reinstalled.
Bleed :
In one pipe operation, the easy flow bleeder valve must be loosened to bleed the system. Bleeding in two pipe operation is automatic, but it may be accelerated by loosening the easy flow bleeder.