PUMP V
Two stage PUMP
The Webster V Serie oil pump is for high capacity of commercial, industrial and institutional heating application. This pump is also designed for use with heavy oil. Pumps are rated : For single stage unit : up to 180 GPH with #2 fuel oil, to 270 GPH with 1000 SSU For two-stage unit : up to 145 GPH with #2 fuel oil, to 205 GPH with 1000 SSU.
Compatibilité



One pipe installation :
V pumps are not recommended for us in one pipe system.
Two pipe installation :
The steel plug of the inlet port must be removed and the bypass plug must be inserted in the applicable inlet port allowing excess fuel is bypassed back to the tank. The return plug must not be reinstalled.
V serie pumps are shipped from the factory set for 2 pipe system.
Bleed :
Bleeding in two pipe operation is automatic for two-stage pump and most single stage pump. To bleed manually the system loosened pressure gauge port.